DOB05/13/2025OBSERVED AT EXOSURE 1 MULTIPLE DEFECT ALONG PARAPET AREA CRACK & SPALLED STONES, CRACK AT 1ST FLOOR. EXP 2 CRACK, DAMAGED JOINTS AND CRACK PANE. EXP3 CRACK 1FL CORNER OF EXPOSURE 4. EXPOSURE 4 BROKEN WINDOW PANE, AND CRACK AT CORNER AT EXPOSURE 1. OBSERVED CORROSION OF GATES. REMEDY: MAINTAIN BUILDING REPAIR AND/OR REPLACE
ECB02/06/2026CLASS 1 RTS CONT: WHEELCHAIR PLATFORM LIFT IS NOT READILY OPERABLE. REQUIRED OPERATING KEY WAS NOT AVAILABLE ON PREMISES UPON INSPECTION AND WAS IN POSSESSION OF ELEVATOR CONTRACTOR. DEVICE THEREFORE NOT AVAILANothing owed — awaiting certificate of correction
ECB12/24/2025OBSERVED ON THE FIRST FLOOR A BOLT MISSING ON THE SPRINKLER SYSTEM, TRAP WRAP INSULATION IS MISSING ON TRAPS UNDER THE SINKS IN BATHROOMS. KITCHEN SINK WASTE LINE BACKING UP WHICH IS CONTRARY TO CODE SECTION PCNothing owed — awaiting certificate of correction
ECB12/24/2025SPRINKLER HEADS ARE OBSTRUCTED THROUGHOUT THE BUILDING. ON THE SECOND FLOOR, SPRINKLER HEADS ARE DAMAGED, AND PVC WASTE LINES ARE INSTALLED BEHIND WASHING MACHINES. ON FIRST FLOOR STEAM LINE INSTALLED IN THE DENothing owed — awaiting certificate of correction
ECB07/09/2025FAILURE TO PROVIDE UNOBSTRUCTED EXIT PASSAGEWAY. NOTE: AT THE TIME OF INSPECTION OBSERVED ITEMS STORED AT FIRE ESCAPE LANDING AT EXPOSURE 3.REMEDY: REMOVE EGRESS OBSTRUCTION.Nothing owed — awaiting certificate of correction
ECB04/10/2025CLASS 2 ITEMS: IN-CAR EMERGENCY LIGHT INOPERATIVE. PROVIDE AN UPDATED MAINTENANCE LOG. PROVIDE A MAINTENANCE PROGRAM.Nothing owed — awaiting certificate of correction
ECB04/10/2025FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER. SERVICE ELEVATOR EQUIPMENT AS PER BC3001.2 & 27-987. UPON INSPECTION, THE DEVICE IS FOUND TO BE OUT OF SERVICE, CREATING A HAZARDOUS CONDITION PER 1RCNY 11Nothing owed — awaiting certificate of correction
ECB04/10/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: NO FIRE STOPPING PER BC 712.3 (2014 CODE); 27-345; BC 711.2.4 (2022 CODE. OBSERVED UNPERMITTED PLASTIC ACCESS PANELS AT 2ND FLOOR ADJACENT TO DEPT OF HOUSINothing owed — awaiting certificate of correction
ECB04/10/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER: USE OF PROHIBITED DOOR AND/OR HARDWARE PER BC 1008.1.8 (2014 CODE); 27-371; BC 1008.1.9 (2014 CODE); BC 1010.1.8 (2022 CODE); BC 1010.1.9 (2022 CODE). OBSENothing owed — awaiting certificate of correction
ECB04/10/2025FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. DENIED ACCESS TO ROOF LEVEL. COULD NOT CHECK PARAPET WALLS NOR THE ROOF DOOR. POTENTIAL FIRE HAZARD., PROVIDE LEGAL HARDWARENothing owed — awaiting certificate of correction
ECB06/11/2024DEVICE FOUND OUT OF SERVICE. RESTORED TO SERVICE IMMEDIATELY AND CONTACT NYCDOB . AT EIR@BUILDINGS.NYC.GOV FOR A COMPLETE INSPECTION.Nothing owed — awaiting certificate of correction
ECB06/11/2024OBSERVED IN THE SPRINKLER ROOM LOCATED ON THE MAIN FLOOR, FIRE PUMP TRANSFER SWITCH AND ELECTRIC FIRE PUMP CONTROLLER ARE IN THE OFF POSITION. ABSOLUTELY NO WAY OF KNOW IN STREET PRESSURE IS ADEQUATE. AS PER 10Nothing owed — awaiting certificate of correction
ECB06/05/2024OBSERVED IN THE KITCHEN LOCATED ON THE FIRST FLOOR ACTIVE LEAK UNDER THE SINK ON THE WASTE PIPING. AS PER PC 102.3 MAINTENANCE. INSTALLATIONS, BOTH EXISTING AND NEW, AND PARTS THEREOF SHALL BE MAINTAINED IN PRONothing owed — awaiting certificate of correction
ECB03/27/202397/X/17,RESTORE TO SERVICE FOR PROPER INSPECTION BY DOB.Nothing owed — awaiting certificate of correction
ECB01/10/2023LIFT IS CURRENTLY OUT SERVICE AND NEEDS TO BE REPAIREDNothing owed — awaiting certificate of correction
ECB12/13/2021FOUND TO HAVE CORRODED COIL PLATE AND CORRODED PIPING AT COIL, EXPOSED WIRING AT BURNER, GLASS GAUGE GUARDS MISSING. BODY DRAINS MISSING ON SAFETY RELIEF VALVES.Nothing owed — awaiting certificate of correction
ECB12/13/2021FOUND CORRODED WATER COLUMN, GLASS GAUGE GUARDS MISSING, BODY DRAINS MISSING AT SAFETY RELIEF VALVES.Nothing owed — awaiting certificate of correction
ECB09/23/2021NOTED: OBSERVED FIREPROOF SELF-CLOSING DOORS AT 2ND. FLOOR B-WING CORRIDOR "G" NOT SELF-CLOSING, 1ST. FLOOR ENTRANCE FPSC DOORS TO THE "A" AND "B" WINGS DO NOT SELF-CLOSE DUE TO MISSING DOOR DOOR CLOSING HARDWANothing owed — awaiting certificate of correction
ECB10/04/2019NOTED: OBSERVED FIREPROOF SELF CLOSING DOORS AT STAIR A2, 2ND FLOOR CORRIDOR AT B WING, 1ST FLOOR WEST WING, 1ST FLOOR B WING, B WING DOOR LEADING TO ARMORY AREA, 1ST FLOOR A WING, AND CAFETERIA DOOR ALL REMAINNothing owed — awaiting certificate of correction
ECB09/30/2019NOTED: OBSERVED THROUGHOUT BOILER ROOM/GAS METER ROOM/SPRINKLER SHUT OFF VALVE ROOM. HORIZONTAL STEEL BEAMS ARE EXPOSED DUE TO FIREPROOFING COATINGS FALLING OFF, PIPE PENETRATING THROUGH CONCRETE SLAB CEILING ANothing owed — awaiting certificate of correction
ECB09/20/2019LEAK ON CAST IRON FITTING IN THE BOILER ROOM, REPAIR AND/OR REPLACENothing owed — awaiting certificate of correction
ECB04/01/2019FAILURE TO MAINTAIN BLDG IN CODE COMPLIANCE MANNER. OBSERVED ON 4/01/19 @ ABOVE ADDRESS ACTIVE LEAK OF HOT WATER LINES IN BOILER ROOM LOCATED IN MAIN FLOOR. REMEDY: REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB04/01/2019EXIT DOOR NOT SELF CLOSING.NOTED:OBSERVED AT 2ND FLOOR STARR EXIT DOOR2A IS RUBBING ON FLOOR AND DOES NOT SELF CLOSE AT THE BWING OF THE 2NDFL.FIRST FLOOR FPSC DOORS AT BWING IS RACKED AND DETACHED FROM THE TOPNothing owed — awaiting certificate of correction
ECB04/01/2019FAILURE TO MAINTAIN BDLG IN CODE COMPLIANT MANNER.NOTED:OBSERVED AT FLFIRST FLOORS BOILER ROOM SPALLING CONCRETE,CRACKS AND MISSING FALLEN SECTIONS OF CONCRETE THROUGHOUT CEILING AT VARIOUS LOCAITONS.EXPOSED BNothing owed — awaiting certificate of correction
ECB02/11/2019B254,15,34B,50A,50B,50C,50D,50E,50F. B254. 50A-STORAGE IN BOILER ROOM50B-FRESH AIR FAN NOT WORKING; 50C-WRONG DIVERTER ON DUEL FUEL BOILER;50D-SMOKE ALARM NOT WORKING; 50E-F() DEVERTER ON FLUE TO BE REMOVED;Nothing owed — awaiting certificate of correction
ECB10/17/2018FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER:NO FIRE STOPPINGPER BC 712.3;27-345. NOTED:OBSERVED WITHIN BOILER ROOM-PIPE PENETRATIONS AND HOLES IN WALLS AND CEILING W/ NO FIRE STOPPING PROVIDED AT VARINothing owed — awaiting certificate of correction
ECB10/17/2018FAILURE TO COMPLY W/ THE COMMISSIONER'S ORDER CONTAINED IN SUMMONS/VIOLATION#35326114X ISSUED ON 4/12/18, AND TO FILE A CERTIFICATE OF CORRECTION PURSUANT TO 28-201.1 AND 1RCNY 102-01. FOR OCCUPANCY CONTRARY OFNothing owed — awaiting certificate of correction
ECB07/17/201850A-H. AS PER CLASS 2(B254)28-301.1,FAILURE TO MAINTAIN.(50A)INSULATION FAILING OFF BOILER O2.(50B)EXPOSED ELECTRICAL WIRES NEAR FRESH AIR FAN.(50C)NO FUEL OIL SHUT-OFF VALVE & ANTISIPHONE ON SUPPLY LINE.(50D)FNothing owed — awaiting certificate of correction
ECB04/12/2018OCCUPANCY CONTRARY TO THAT ALLOWED BY THE COFO OR BUILDING DEPARTMENT RECORDS.NOTED:AT 2ND STORY ROOMS DESIGNATED FOR OFFICE SPACE NOW BEINGUSED AS SLEEPING QUARTERS(DORM SETUP)REM:DISCONTINUE ILLEGAL OCCUPANCYNothing owed — awaiting certificate of correction
ECB01/04/2018FAILURE TO COMPLY W/THE COMM'S ORDER CONTAINED IN SUMMONS/VIO #35294392M ISSUED ON 11/27/17 & TO FILE A CERT OF CORRECTION PURSUANT TO 28-201.1 & 1RCNY 102-01.FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER.RNothing owed — awaiting certificate of correction
ECB12/12/2017CEASE USE. 5X10,48Y13. (5X)DOOR RESTRICTOR INOPERATIVE. THIS DEVICE IS TO ENSURE THE SAFETY OF ITS REGISTER, REGISTER. (48Y)CONNECTIONS OF PIPING FROM OIL TANK IS LEAKING OIL, SEAL.Nothing owed — awaiting certificate of correction
ECB11/29/201715,32A,42,50A-D. (50)NEED TO CLEAN DEBRIS FROM FRESH AIR FAN & REPLACE SCREW. (50A)NEED TO INSTALL SAIL SWITCH ON FRESH AIR FAN. (50B)MISSING NUTS FOR REAR DOOR OF BOILER. (50C)WEED TO HAVE GLASS PUT ON REAR DONothing owed — awaiting certificate of correction
ECB11/27/2017FAILURE TO MAINTAIN BUILDING IN CODE-COMPLIANT MANNER. 1ST FLOOR LEVEL BOILER ROOM, LEAKED AND RUSTED PIPE ON WEST SIDE, ON EASTSIDE MAIN WATER LINES AND PRESSURE PUMPS ARE DETERIORATED AND LEAKING NON-STOP. RENothing owed — awaiting certificate of correction
ECB11/04/2017RE ISSUED #35286783J DATED 7/25/17 OCCUPANCY CONTRARY TO THAT ALLOWED ON DOB RECORDS AND 2ND FLOOR OFFICES BEEN USED AS A SLEEPING AREA. REMEDY: DISCONTINUE ILLEGAL OCCUPANCY OR AMEND C OF ONothing owed — awaiting certificate of correction
ECB10/16/2017FAILURE TO MAINTAIN BUILDING IN CODE COMPLIANT MANNER.1ST FL. LEVEL B OILER ROOM LEAKED AND RUSTED PIES ON WEST SIDE PIPE LEAKED CONTINALLY BEHIND WATER TANK ON EAST SIDE MAIN WATER LINES PRESSURE-PUMPS ISNothing owed — awaiting certificate of correction
ECB09/05/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER;NO FIRE STOPPING PER BS 712.3;27-345,NOTED (GROUND FL) ELECTRICAL ROOM HOLES IN FL & WOOD FLS,ELECTRICAL ROOM BY (KITCHEN) HOLES IN WALLS BOILER ROOM HOLES IN WNothing owed — awaiting certificate of correction
ECB07/25/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER.CELLAR-BOILER ROOM LEAKING/RUSTED PIPES.REM REPAIR/REPLACENothing owed — awaiting certificate of correction
ECB07/25/2017OCCUPANCY CONTRARY TO THAT ALLOWED BY C OF O OR DOB RECORDS.2ND FL OFFICES BEING USED AS SLEEPING AREAS.REM DISCONTINUE ILLEGAL OCCUPANCYNothing owed — awaiting certificate of correction
ECB04/14/2017OCCUPANCY CONTRARY TO THAT ALLOWED BY THE CERTIFICATE OF OCCUPANCY OR BUILDING DEPARTMENT RECORDS.NOTED:AT 2ND FLOOR LEVEL OFFICE IS BEING OCCUPIED AS ROOM FOR LIVING PURPOSE,CONTRARY TO BUILDING RECORDS JOBNothing owed — awaiting certificate of correction
ECB03/30/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED: 1)IN A ROOM ON 1ST FL A HOSE LOCK(BOILER DRAIN)INSTALLED ON THE FD CHECK VALVUEINSTEAD OF THE REQUIRED BALL DRIPS & 2)ON TWO FLOORS NO PRESSURE GAUGENothing owed — awaiting certificate of correction
ECB03/30/2017FAILURE TO MAINTAIN BLDG IN CODE COMPLIANT MANNER. OBSERVED IN THE BOILER ROOM A RETURN CONDENSATE LINE RUSTED & LEAKING IN SEVERAL PLACES & FLOODING THE BOILER ROOM. REMEDY: REPAIR &/OR REPLACE.Nothing owed — awaiting certificate of correction
ECB03/30/2017FAILURE TO MAINTAIN BLDG IN CODE-COMPLIANT MANNER. OBSERVED IN THE BOILER ROOM. 1)A FUTURE CONNECTION INSTALLED ON GAS PIPING CONTRARY TO CETION 408.2 OF THE FUEL GAS CODE & 2)NO SHUT OFF VALVE INSTALLED W/INothing owed — awaiting certificate of correction
ECB07/21/2016FAILURE TO MAINTAIN BLDG CODE COMPLIANT. NOTED: @ WEST 168 ST THE 9TH WINDOW RIGHT OF 651 ENTRY, CRACKED, BULGING, LOOSE BRICK MASONRY OF WINDOW GUARD ANCHOR POINT. ALSO LOOSE HAND CAP RAMP HAND RAILING OFFERINNothing owed — awaiting certificate of correction
ECB07/21/2016OCCUPANCY CONTRARY TO DOB RECORDS. NOTED: ROOM 102- DINING ROOM- AS A PLACE OF ASSEMBLY W/ MAXIMUM OCCUPANCY SIGN POSTED FOR 78 PERSONS. ROOM ARRANGED W/ SEATING FOR 106 PERSONS. ROOM HAS ONE EXIT DOOR W/ ILLUMNothing owed — awaiting certificate of correction
ECB03/11/2016EXIT DOOR NOT SELF-CLOSING.THE FOLLOWING DOORS NOT SELF-CLOSING:2ND FLR STAIRWAY EXIT DOOR "B",1ST FLR "A" WING EXIT DOORS(ROOM 126-130),1STFLR "A" WING EXIT DOORS (ROOM 108-111),BOILER ROOM DOOR#124 & 1ST FLRNothing owed — awaiting certificate of correction
ECB08/12/2014/42L09/05L10/ 42L09-JUMPERS ON CONTROLLER TOP. 05L10-ZONE RESTRICTOR.Nothing owed — awaiting certificate of correction